Product Detail |
Series |
|
REALCOMP |
Model |
|
Realcomp Controller |
Type |
|
Automatic Power Factor Controller |
Auxiliary supply |
Rated Auxiliary supply voltage Us |
min |
100V AC |
|
max |
415V AC |
|
min |
110V DC |
|
max |
250V DC |
Auxiliary operating range |
|
90…484V AC / 93.5…300V DC |
Auxiliary rated frequency |
|
50/60 Hz ±10% |
Power consumption |
max |
27 VA (with 4 expansion modules) |
Power dissipation |
max |
10.5 W (with 4 expansion modules) |
|
|
2.5 W (with no expansion modules) |
Immunity time for microbreakings |
|
≥35 ms (110V AC); |
|
|
≥80 ms (220…415V AC) |
Voltage inputs |
Rated Voltage (Ue) |
phase-phase |
600V AC (rated max.) |
Operating Voltage range |
phase-phase |
50…720V AC |
|
phase-neutral |
415V AC |
Frequency range |
min |
45…..65 Hz |
|
max |
360…..440 Hz |
Type of Measure |
|
True RMS value |
No-voltage release |
|
≥8 ms |
Measurement input impedance |
phase-phase |
>1.10 MΩ |
|
phase-neutral |
>0.55 MΩ |
Type of Connection |
|
Single phase, two phase, three phase with or without neutral or balanced three phase system |
Current Inputs |
Number of Current input |
|
3 Nr |
Type of Input |
|
Shunt supplied by external current transformer (low voltage), Max 5A |
Measurement range |
|
0.025…6A ~ for 5A scale |
|
|
0.025…1.2A ~ for 1A scale |
Measurement method |
|
True RMS value |
Constant overload |
|
1.2 le |
Overload peak |
|
50A for 1s |
Burden per phase |
|
<0.6 VA |
Measurement Data |
Type of voltage and current measurement |
|
True RMS value |
Power Factor adjustment |
|
0.5 ind…0.5 cap. |
Type of temperature sensor |
|
Internal + PT100 with expansion module |
Temperature measurement range |
|
0…+212°C |
Alarms |
Number of Alarms |
|
8 |
Type of Alarms |
|
User programmable |
Communication |
Communication Port |
|
RS-485 (with expansion module) |
Communication Protocol |
|
Modbus-RTU, ASCII and TCP |
Relay Outputs |
Number of relay output |
|
0 N° (up to 10 with expansion module) |
Static Outputs |
Number of static output |
|
8 (up to 24 with expansion module) |
Rated Current |
|
120 mA max. 40V DC / 30V AC |
Insulations |
Rated insulation voltage Ui |
|
600 V |
Rated impulse withstand voltage Uimp |
|
9.5 kV |
Operating frequency withstand voltage |
|
5.2 kV |
Connections |
Type of Terminal |
|
Plug-in, removable |
Conductor Cross section |
min |
0.2 mm2 |
|
max |
2.5 mm2 |
|
min |
24 AWG |
|
max |
12 AWG |
Tightening torque |
max |
0.56 Nm |
|
|
5lbin |
Ambient Temperature |
Temperature Operating temperature |
min |
-20°C |
|
max |
+70°C |
Temperature Storage temperature |
min |
-30°C |
|
max |
+80°C |
Relative humidity |
|
<80% |
Maximum Pollution degree |
|
2 |
Overvoltage category |
|
3 |
Measurement category |
|
III |
Shock resistance |
|
15g |
Vibration resistance |
|
0.7g |
Housing |
Execution |
|
Flush mount |
Material |
|
Polycarbonate |
Mounting |
|
Flush-mount, 144x144mm (5.67″ x 5.67″) |
Degree of Protection |
|
IP65 on Front, IP20 terminals |
Dimensions (W x H x D) |
|
144mm x 144mm x 53.2mm |
Weight |
|
980 Gram |
Expansion Slot |
|
4 |