NAAC REALCOMP™ THYRISTOR MODULES

- Real-Time Dynamic Power Factor Correction
- Integrated CT for Monitoring and Protection of Current, Power and Harmonics in the Capacitor Banks
- Programmable Protection Thresholds
- Programmable Relay Output for Alarm Signalling or Fan Control
- Monitoring and Diagnostics of the Integrated Cooling System
- NFC Enabled for Convenient Programming of the Parameters via Smartphone/Tablet
- Can be Controlled via the Serial Port using the Optional RS-485 port with the combination of the REALCOMP™ Controller
- Compatible with the Mobile App for viewing Measurements, Events and Active Alarms and for Sending Commands and Configuring Parameters
- Silent Operation as the Switching of Capacitors is Managed Electronically
- Switching ON at zero-crossing
- Overtemperature Protection via Integrated Probe or an External Input Probe
- Supports Vertical and Horizontal installation
- 3 status LEDs – POWER, ON and FAULT
- Front Optical Port for Connecting to a PC via USB or Wi-Fi
Technical Specifications - REALCOMP™ THYRISTOR MODULES
NAAC REALCOMP™ Thyristor Switching Modules (60 and 120 KVAR)
| Product Details | ||
| Series | REALCOMP | |
| Models available | REALCOMP Thyristor Switching Module – 60 KVAR and 120 KVAR at 480V |
|
| Type | SCR | |
| General Characteristics | ||
| Rated Voltage | 400V…480V | |
| Operating Voltage Range | 340V…528V | |
| Rated Frequency | 50/60 Hz | |
| Operating Frequency Range | 45Hz…65Hz | |
| Rated Current (Ie) | 60 KVAR | 72A |
| 120 KVAR | 144A | |
| Step Power at (for 60 KVAR and 120 KVAR models) | 400V AC | 50 KVAR and 100 KVAR |
| 440V AC | 55 KVAR and 110 KVAR | |
| 480V AC | 60 KVAR and 120 KVAR | |
| Peak Inverse Voltage (PIV) | 2200V AC | |
| Number of Controlled Phases | 2 NO | |
| Control Circuit | 12-24V DC input or free-voltage input or via RS485 serial port (with optional expansion module in combination with REALCOMP Controller + expansion module) | |
| Auxiliary Supply | ||
| Rated Auxiliary Supply Voltage | Min | 100V AC |
| Max | 240V AC | |
| Auxiliary Rated Frequency | 50/60 Hz | |
| Power Consumption | Max | 14.1 VA |
| Power Dissipation | Max | 5.8 W |
| Control Input | ||
| Terminals | CONTROL +/- | |
| Rated Voltage | 12V-24V DC | |
| Operating Range | 8V…30V DC | |
| Digital Inputs | ||
| Terminals | C-IN1 | |
| Applied Voltage at Contact (Internal) | 5V DC | |
| Input Current | < 10 mA | |
| Low Input Signal | < 0.8V DC | |
| High Input Signal | > 3.2V DC | |
| Input Signal Delay | > 50 ms | |
| NTC Probe Input | ||
| Terminals | NTC-NTC | |
| Sensor Type | NTC | |
| Measuring Range | -25OC…+85OC | |
| Maximum Connection Length | 3 mt | |
| Fan Power Supply | ||
| Terminals | Fan +/- | |
| Supply Voltage (Internal) | 5V DC (provided by TSM) | |
| Fan Type | 2 built-in fans | |
| Communication | ||
| Communication Port | RS485 (by adding the RS485 card) | |
| Relay Outputs | ||
| Number of Relay Output | 1 NO | |
| Contact Arrangement | 1 C/O- SPDT | |
| Rated Current | NO Contact : AC1 5A 250V AC / 5A 30V DC | |
| NC Contact : AC1 3A 250V AC / 3A 30V DC | ||
| Maximum Switching Voltage | 250V AC | |
| Electrical Life (with rated load) | NO Contact : 10×103 Cycles | |
| NC Contact : 20×103 Cycles | ||
| Mechanical Life | 107 Cycles | |
| Insulations | ||
| Rated insulation voltage Ui | 480V | |
| Rated impulse withstand Voltage Uimp | 4 kV | |
| Connections – Power Terminals (60 KVAR TSM) | ||
| Type of Terminal | Fixed – double lock clamp | |
| Conductor Cross Section | Min. | 2 x 2.5 mm2 |
| Max | 2 x 35 mm2 | |
| Min | 2 x 18 AWG | |
| Max | 2 x 2 AWG | |
| Tightening Torque | Max | 5.5-6.5 Nm |
| Max | 4.6-4.79 Ibft | |
| Connections – Power Terminals (120 KVAR TSM) | ||
| Type of Terminal | Bars – 25x5mm 11 mm hole dia | |
| Conductor Cross Section | Min. | 50 mm2 |
| Max | 1 x AWG 3/0 | |
| Tightening Torque | Max | 35 Nm (42Nm for lugs) |
| Max | 309 in-lbs (375 in-lbs for lugs) | |
| Connections – Relay Output | ||
| Type of Terminal | Screw | |
| Conductor Cross Section | Min. | 0.2 mm2 |
| Max | 4 mm2 | |
| Min | 26 AWG | |
| Max | 10 AWG | |
| Tightening Torque | Max | 0.8 Nm |
| Max | 7 Ibin | |
| Connections – Fan and Digital Input | ||
| Type of Terminal | Screw | |
| Conductor Cross Section | Min. | 0.2 mm2 |
| Max | 2.5 mm2 | |
| Min | 24 AWG | |
| Max | 12 AWG | |
| Tightening Torque | Max | 0.44 Nm |
| Max | 4 Ibin | |
| Ambient Conditions | ||
| Operating Temperature | Min | -20OC |
| Max | +45OC without derating (up to 55OC with derating) | |
| Storage Temperature | Min | -30OC |
| Max | +80OC | |
| Relative Humidity | <80% | |
| Maximum Pollution Degree | 2 | |
| Over Voltage Category | III | |
| Maximum Altitude | 2000m without derating | |
| Shock Resistance | 15g | |
| Vibration Resistance | 0.7g | |
| Housing | ||
| Execution | Internal Panel Version | |
| Material | Polycarbonate | |
| Mounting | 60 KVAR | Screw fixing or DIN-rail with optional accessory |
| Degree of Protection | IP00 | |
| Dimensions (W x H x D) | 60 KVAR | 95 mm x 226 mm x 182 mm |
| Dimensions (W x H x D) with lugs | 120 KVAR | 212 mm x 301 mm x 216 mm |
| Dimensions (W x H x D) with terminal protection | 120 KVAR | 212 mm x 468 mm x 216 mm |
| Weight | 60 KVAR | 2840g |
| 120 KVAR | 6680g | |
| LEDs | ||
| Status LEDs | 3 (POWER-ON-FAULT) | |