NAAC REALCOMP® THYRISTOR MODULES
- Real-time dynamic Power Factor Correction
- Integrated CT for motoring and protection of current, power and harmonics in the capacitor banks
- Programmable protection thresholds
- Programmable relay output for alarm signalling or fan control
- Monitoring and diagnostics of the integrated fan
- NFC Enabled for convenient programming of the parameters via smartphone and tablet
- Can be controlled via the serial port using the optional RS-485 port with the combination of the REALCOMP Controller
- Compatible with the mobile app for viewing measurements, events and active alarms and for sending commands and configuring parameters
- Silent operation as the switching of capacitors is managed electronically
- Switching ON at zero-crossing
- Overtemperature protection via integrated probe or an external input probe
- Monitoring and diagnostics of the integrated fan
- Supports vertical and horizontal installation
- 3 status LEDs – POWER, ON and FAULT
- Front optical port for connecting to a PC via USB or Wi-Fi
Characteristics - REALCOMP® THYRISTOR MODULES
NAAC REALCOMP® Thyristor Switching Modules (60 and 120 KVAR)
Product Detail | ||
Series | REALCOMP | |
Models available | Realcomp Thyristor Switching Module – 60 KVAR and 120 KVAR at 480V |
|
Type | SCR | |
General Characteristics | ||
Rated Voltage | 400V…480V | |
Operating Voltage Range | 340V…528V | |
Rated Frequency | 50/60 Hz | |
Operating Frequency Range | 45Hz…65Hz | |
Rated Current (Ie) | 60 KVAR | 72A |
120 KVAR | 144A | |
Step Power at (for 60 KVAR and 120 KVAR models) | 400V AC | 50 KVAR and 100 KVAR |
440V AC | 55 KVAR and 110 KVAR | |
480V AC | 60 KVAR and 120 KVAR | |
Peak Inverse Voltage (PIV) | 2200V AC | |
Number of Controlled Phases | 2 NO | |
Control Circuit | 12-24V DC input or free-voltage input or via RS485 serial port (with optional expansion module in combination with REALCOMP Controller + expansion module) | |
Auxiliary Supply | ||
Rated Auxiliary Supply Voltage | Min | 100V AC |
Max | 240V AC | |
Auxiliary Rated Frequency | 50/60 Hz | |
Power Consumption | Max | 14.1 VA |
Power Dissipation | Max | 5.8 W |
Control Input | ||
Terminals | CONTROL +/- | |
Rated Voltage | 12V-24V DC | |
Operating Range | 8V…30V DC | |
Digital Inputs | ||
Terminals | C-IN1 | |
Applied Voltage at Contact (Internal) | 5V DC | |
Input Current | < 10 mA | |
Low Input Signal | < 0.8V DC | |
High Input Signal | > 3.2V DC | |
Input Signal Delay | > 50 ms | |
NTC Probe Input | ||
Terminals | NTC-NTC | |
Sensor Type | NTC | |
Measuring Range | -25OC…+85OC | |
Maximum Connection Length | 3 mt | |
Fan Power Supply | ||
Terminals | Fan +/- | |
Supply Voltage (Internal) | 5V DC (provided by TSM) | |
Fan Type | 2 built-in fans | |
Communication | ||
Communication Port | RS485 (by adding the RS485 card) | |
Relay Outputs | ||
Number of Relay Output | 1 NO | |
Contact Arrangement | 1 C/O- SPDT | |
Rated Current | NO Contact : AC1 5A 250V AC / 5A 30V DC | |
NC Contact : AC1 3A 250V AC / 3A 30V DC | ||
Maximum Switching Voltage | 250V AC | |
Electrical Life (with rated load) | NO Contact : 10×103 Cycles | |
NC Contact : 20×103 Cycles | ||
Mechanical Life | 107 Cycles | |
Insulations | ||
Rated insulation voltage Ui | 480V | |
Rated impulse withstand Voltage Uimp | 4 kV | |
Connections – Power Terminals (60 KVAR TSM) | ||
Type of Terminal | Fixed – double lock clamp | |
Conductor Cross Section | Min. | 2 x 2.5 mm2 |
Max | 2 x 35 mm2 | |
Min | 2 x 18 AWG | |
Max | 2 x 2 AWG | |
Tightening Torque | Max | 5.5-6.5 Nm |
Max | 4.6-4.79 Ibft | |
Connections – Power Terminals (120 KVAR TSM) | ||
Type of Terminal | Bars – 25x5mm 11 mm hole dia | |
Conductor Cross Section | Min. | 50 mm2 |
Max | 1 x AWG 3/0 | |
Tightening Torque | Max | 35 Nm (42Nm for lugs) |
Max | 309 in-lbs (375 in-lbs for lugs) | |
Connections – Relay Output | ||
Type of Terminal | Screw | |
Conductor Cross Section | Min. | 0.2 mm2 |
Max | 4 mm2 | |
Min | 26 AWG | |
Max | 10 AWG | |
Tightening Torque | Max | 0.8 Nm |
Max | 7 Ibin | |
Connections – Fan and Digital Input | ||
Type of Terminal | Screw | |
Conductor Cross Section | Min. | 0.2 mm2 |
Max | 2.5 mm2 | |
Min | 24 AWG | |
Max | 12 AWG | |
Tightening Torque | Max | 0.44 Nm |
Max | 4 Ibin | |
Ambient Conditions | ||
Operating Temperature | Min | -20OC |
Max | +45OC without derating (up to 55OC with derating) | |
Storage Temperature | Min | -30OC |
Max | +80OC | |
Relative Humidity | <80% | |
Maximum Pollution Degree | 2 | |
Over Voltage Category | III | |
Maximum Altitude | 2000m without derating | |
Shock Resistance | 15g | |
Vibration Resistance | 0.7g | |
Housing | ||
Execution | Internal Panel Version | |
Material | Polycarbonate | |
Mounting | 60 KVAR | Screw fixing or DIN-rail with optional accessory |
Degree of Protection | IP00 | |
Dimensions (W x H x D) | 60 KVAR | 95 mm x 226 mm x 182 mm |
Dimensions (W x H x D) with lugs | 120 KVAR | 212 mm x 301 mm x 216 mm |
Dimensions (W x H x D) with terminal protection | 120 KVAR | 212 mm x 468 mm x 216 mm |
Weight | 60 KVAR | 2840g |
120 KVAR | 6680g | |
LEDs | ||
Status LEDs | 3 (POWER-ON-FAULT) |